Products specific for Baltic
  • High voltage aluminium cable 76/132 (145) kV
  • High voltage aluminium cable 87/150 (170) kV
  • High voltage copper cable 76/132 (145) kV
  • Multipurpose medium voltage power cable 12/20 (24) kV
  • Multipurpose medium voltage power cable 6/10 (12) kV

Products specific for Denmark

Products specific for Norway

  • Kraftkabel for høyspenning 12/20 (24) kV
  • Kraftkabel for høyspenning 36/60 (72,5) kV
  • Kraftkabel for høyspenning 6/10 (12) kV
  • Kraftkabel for høyspenning 87/150 (170) kV

Products specific for UK

  • High voltage aluminium cable 76/132 (145) kV
  • High voltage copper cable 76/132 (145) kV
REKA kaapeli
dryrex

Medium voltage cable AXQJ-F LT

6/10 (12) kV
SS 424 14 16 when applicable

For fixed installation indoors and outdoors. In cable ducts and trays. Especially for applications where halogenfri flame retardant burning characterics in case of fire are essential. Also for buried into ground. Not suitable for submarine applications or similar.

Conductor Watertight round stranded and compacted aluminium conductor
Special property Self extinguishing and fire retardant when installed in bunches
Fire class F4B 3x and F4C 1x »
Conductor screen Semiconductive halogenfri cross-linked polyethylene
Insulation Extruded cross-linked polyethylene
Insulation screen Semiconductive halogenfri cross-linked polyethylene
Metallic screen Layer of helically wound bare copper wires with a copper equalization tape. A lapped plastic tape over the metallic screen as a binder.
Sheath Black sheath made of halogenfree flame retardant polyolefin compound.
Min.handling temperature ºC -15
Max. conductor temperature ºC +90
Conductor shortcircuit temperature 5 s ºC +250
Product number Size Diameter [mm] Weight [kg/km] Maximum allowed bending radius in installation [cm] Maximum allowed bending radius in final installation [cm]
1186262 1x50/16 24 670 36 24
1186264 1x95/25 27 950 41 27
1186266 1x150/25 31 1180 47 31
1186268 1x240/35 35 1650 53 35
1186270 1x400/35 41 2200 62 41
1186272 1x630/35 47 3110 71 47
1187723 3x50/16 46 1810 69 46
1187725 3x95/25 53 2640 80 53
1187727 3x150/25 60 3450 90 60
1187729 3x240/35 70 4870 105 70
Size Maximum allowed pulling force when pulling from conductors [kN] Maximum allowed pulling force when pulling with cable stocking [kN] Maximum DC-resistance of phase conductor +20°C [ohm/km] Maximum AC-resistance of phase conductor, +65°C [ohm/km] Induktance, cables in triangle [mH]
1x50/16 2.5 0.75 0.641 - 0.41
1x95/25 4.75 1.425 0.32 - 0.36
1x150/25 7.5 2.25 0.206 - 0.34
1x240/35 12 3.6 0.125 - 0.32
1x400/35 20 6 0.0778 - 0.30
1x630/35 20 8.5 0.0469 - 0.28
3x50/16 7.5 2.25 0.641 - 0.54
3x95/25 14.25 4.275 0.32 - 0.50
3x150/25 20 6.75 0.206 - 0.48
3x240/35 20 8.5 0.125 - 0.45
Size Induktance, cables on level [mH] Operating capasitance [µF/km] Current carrying capacity in soil, conductor +65°C [A] Current carrying capacity in air, conductor +90°C [A] Thermal shortcut current of conductor, 1 s, [kA]
1x50/16 0.59 0.23 - - 4.7
1x95/25 0.55 0.29 - - 8.9
1x150/25 0.53 0.35 - - 14.1
1x240/35 0.50 0.43 - - 22.6
1x400/35 0.48 0.53 - - 37.8
1x630/35 0.46 0.64 - - 59.5
3x50/16 - 0.23 145 160 4.7
3x95/25 - 0.29 205 230 8.9
3x150/25 - 0.35 260 305 14.1
3x240/35 - 0.43 340 400 22.6
Size Thermal shortcut current of metallic screen, 1 s [kA] Packing [m]
1x50/16 2.3 T 500 K14
1x95/25 3.4 T 500 K14
1x150/25 3.4 T 500 K16
1x240/35 4.7 T 500 K18
1x400/35 4.7 T 500 K18
1x630/35 4,7 T 500 K20
3x50/16 2.3 T 500 K20
3x95/25 3.4 T 500 K22
3x150/25 3.4 T 500 K24
3x240/35 4.7 T 500 K26
dryrex
Reka Product Support Service  Reka Cables maintain this Product Support Service for use of customers of Reka Cables Ltd and customers of Reka Corporation. From the Service customers can load and obtain in e-form product – and support material for Reka Products for their own business needs. Reka Product Support Service can be used by all customers, who approve these conditions.  The use of Reka® trade mark and the material obtainable from the Product Support Service is limited to the normal conduct of business of customers and to connection thereof, but provided that that the use will not defame the Reka® trade mark and is not in conflict with good business manners. The right of use of use is free of charges and valid until further notice.  The customer is not allowed to convey the material loaded or printed from Reka Product Support Service, except in normal connection to business for purposes such as planning, advertising and the like or as attached to such material. The origin of the material must be mentioned in connection thereof.  Reka® trade mark and the material obtainable in e-form from Reka Product Support Service, as well as the copyrights related thereof, are property of Reka Cables Ltd and in connection with copying or printing these rights will not be conveyed of transferred to the customer even in part. Reka Cables Ltd guarantees that these materials, which can be printed or loaded from the site, do not infringe immaterial rights of third parties.  Reka Cables Ltd reserves the right to close the Product Support Service without prior notice and reserves the right to limit or prevent the use of the Product Support Service by certain identified users without prior notice.  The pages of Reka Product Support Service can be used in the form as they appear at each occasion. Reka Cables Ltd has done its best to ensure that the information is correct and up-to-date, but it can nor be guaranteed that the pages could not contain unintended mistakes or out-of-date information. Reka Cables Ltd underlines that technical information and price information on the pages is not binding.  Reka Cables Ltd is not liable for damages, which may result in relation with mistakes or incorrect information on the pages or files of Reka Product Service, malfunction of the pages or with use of information obtainable from the pages without separately confirming from Reka Cables Ltd that the information used is correct and up-to-date.